Quartz Elec - leading electrical engineering group

H.V. terminal boxes

Quartzelec supplies a complete range of certified and uncertified main and neutral terminal boxes, suitable for 3.3kV applications and above. ATEX certification is in place for hazardous area applications. IECEx certification is also available for certain terminal boxes.

Phase Segregated – PSE/PSN

Maximum rating: 11kV, 810A (uncertified), 11kV, 545A (certified). ATEX and IECEx certified to Ex e and Ex n. Fault Capacity: 250MVA @ 3.3kV, 500MVA @ 6.6kV, 833MVA @ 11kV. Fault tested at 44kA for 0.25 secs.

Euromold – EIE/ETE/EIN/ETN

Inline and Triangular Arrangements. Maximum rating: 15kV, 1250A (uncertified), 11kV, 1250A (certified). ATEX certified to Ex e and Ex n. Fault tested at 43.8kA for 0.25 secs.

Air Insulated – AIE

Maximum rating: 11kV (certified) 900A, 15kV (uncertified) 1250A Connectors. ATEX certified to Ex e. Fault Capacity: 500MVA @ 6.6kV. Fault tested at 22.1kA for 0.25 secs. (Historical data)

Weatherproof – WPN

Maximum rating: 6.6kV, 700A (11kV Neutral). ATEX certified to Ex n. Fault Capacity: 500MVA @ 6.6kV. Fault tested at 22.1kA for 0.25 secs. (Historical data)

Phase Insulated (BEAMA/CEGB) – BEE/BEN

Maximum rating: 3.3kV, 530A (uncertified and certified) ATEX certified to Ex e and Ex n. Fault Capacity: 250MVA @ 3.3kV. Fault tested at 26.3kA for 0.25 secs. (Historical data)

Protection Enclosure - PEN

Maximum rating: 15kV, 2000A (uncertified), 13.8kV, 2000A (certified) ATEX certified to Ex n.

Contact our nearest expert:

Contacts: James Kane
Quartzelec – Aberdeen
51 York Street, Aberdeen, AB11 5DP
T: 01224 593008
F: 01224 592844

E: aberdeen@quartzelec.com

Technical data

Expert contact details:

Contacts: James Kane
Quartzelec – Aberdeen
51 York Street, Aberdeen, AB11 5DP
T: 01224 593008
F: 01224 592844
E: aberdeen@quartzelec.com

Related Downloads